26SI Series Alternator – Data Link Configuration



Illustration 1 g01720155

Refer to Illustration 1. The “Cat Data Link Module Identifier Configuration” (1) selection is for CDL communications only. The PL1000E is able to select from three different MID numbers. The “Cat Data Link Module Identifier Configuration” (1) is NOT available on the “CAN/J1939” network as a dynamic protocol.

Cat Data Link Module Identifier Configuration

Possible values follow:

  • PL1000 #1

  • PL1000 #2 (Default)

  • PL1000 #3

Cat Data Link Boost Function Enable Status

Possible values follow:

  • Enabled

  • Disabled (Default)


NOTICE

CDL Boost should be enabled only if the wiring lengths for the harnesses are 30.5 m (100 ft) or greater. If the wiring lengths for the harnesses are under 30.5 m (100 ft), then CDL Boost may cause failure.