Illustration 1 | g01720155 |
Refer to Illustration 1. The “Cat Data Link Module Identifier Configuration” (1) selection is for CDL communications only. The PL1000E is able to select from three different MID numbers. The “Cat Data Link Module Identifier Configuration” (1) is NOT available on the “CAN/J1939” network as a dynamic protocol.
Cat Data Link Module Identifier Configuration
Possible values follow:
- PL1000 #1
- PL1000 #2 (Default)
- PL1000 #3
Cat Data Link Boost Function Enable Status
Possible values follow:
- Enabled
- Disabled (Default)
|
NOTICE |
---|
CDL Boost should be enabled only if the wiring lengths for the harnesses are 30.5 m (100 ft) or greater. If the wiring lengths for the harnesses are under 30.5 m (100 ft), then CDL Boost may cause failure. |
|