26SI Series Alternator – Modbus Configuration



Illustration 1 g01743935

ModBus Configuration Details

ModBus #1 Port Selection

The ModBus #1 Port selections are:

  • Disabled

  • Serial Port #1 (default)

  • Serial Port #2

  • Serial Port #4

ModBus #1 Baud Rate

The ModBus Baud Rates selections are:

  • 1200

  • 2400

  • 4800

  • 9600 (default)

  • 19200

  • 38400

  • 57600

ModBus #1 Echo/No Echo

The ModBus #1 Echo/No Echo selections are:

  • Echo

  • No Echo (default)

ModBus #1 Flow Control

The ModBus #1 Flow Control selections are:

  • Hardware (CTS/RTS)

  • None (default)

  • Reserved

  • Software (Xon/Xoff)

ModBus #1 Data Size

The ModBus #1 Data Size selections are:

  • 7

  • 8 (default)

ModBus #1 Parity

The ModBus #1 Parity selections are:

  • Even

  • Mark

  • No Parity (default)

  • Odd

  • Space

ModBus #1 Data Link Address

The ModBus #1 Data Link Address selections are any value between zero (0) and 254. It is recommend that the value remain at default.

The default value is 254.

ModBus #2 Port Selection

The ModBus #2 Port selections are:

  • Disabled

  • Serial Port #1

  • Serial Port #2 (default)

  • Serial Port #4

ModBus #2 Baud Rate

The ModBus #2 Baud Rate selections are:

  • 1200

  • 2400

  • 4800

  • 9600 (default)

  • 19200

  • 38400

  • 57600

ModBus #2 Echo/No Echo

The ModBus #2 Echo/No Echo selections are:

  • Echo

  • No Echo (default)

ModBus #2 Flow Control

The ModBus #2 Flow Control selections are:

  • Hardware (CTS/RTS)

  • None (default)

  • Reserved

  • Software (Xon/Xoff)

ModBus #2 Data Size

The ModBus #2 Data Size selections are:

  • 7

  • 8 (default)

ModBus #2 Parity

The ModBus #2 Parity selections are:

  • Even

  • Mark

  • No Parity (default)

  • Odd

  • Space

ModBus #2 Data Link Address

The ModBus #2 Data Link Address selections are any value between zero (0) and 254. It is recommend that the value remain at default.

The default value is 254.

ModBus #3 Port Selection

The ModBus #3 Port Selection selections are:

  • Disabled

  • Serial Port #1

  • Serial Port #2

  • Serial Port #4 (default)

ModBus #3 Baud Rate

The ModBus #3 Baud Rate selections are:

  • 1200

  • 2400

  • 4800

  • 9600 (default)

  • 19200

  • 38400

  • 57600

ModBus #3 Echo/No Echo

The ModBus #3 Echo/No Echo selections are:

  • Echo

  • No Echo (default)

ModBus #3 Flow Control

The ModBus #3 Flow Control selections are:

  • Hardware (CTS/RTS)

  • None (default)

  • Reserved

  • Software (Xon/Xoff)

ModBus #3 Data Size

The ModBus #3 Data Size selections are:

  • 7

  • 8 (default)

ModBus #3 Parity

The ModBus #3 Parity selections are:

  • Even

  • Mark

  • No Parity (default)

  • Odd

  • Space

ModBus #3 Data Link Address

The ModBus #3 Data Link Address selections are any value between zero (0) and 254. It is recommend that the value remain at default.

The default value is 254.

ModBus TCP Data Link Address

The ModBus TCP Data Link Address selections are any value between zero (0) and 254. It is recommend that the value remain at default.

The default value is 254.

RS-485 Mode

The “RS–485 Mode” configuration item only appears on the 285-1138 Electronic Control Modules or newer. The “RS–485 Mode” selections are as follows:

  • 2 – wire (half duplex)

  • 4 – wire (full duplex) (default)

If a PL1000E is being commissioned in a system that has RS-485 communications, then the appropriate wiring standards must be used for the RS-485 mode.